Wuhan GDMK Electric Co., Ltd.

2nd Floor, Western Color Aluminum Plastic Comprehensive Building, Huangjiahu Avenue, Jiangxia Distri, Switchger Test Equipment, 430200

https://www.mktester.com/hv-switch-tester/switchger-test-equipment.html

Overview:


    Switchger test equipment is mainly applied for ex-work energized testing for high voltage and low voltage cabinet manufacturers. The test bench could provide various AC/DC power source in order to detect switch cabinet.


Main Technical specifications:


1. Input: 3 phase 4 line AC 380V

2.Output voltage and current:

     3 phase AC 0-50A output (10V adjustable) one group

     3 phase AC 100V output (fixed value) one group

 3. AC operating voltage output is AC 0-380V 220V the current is conventional and adjustable.

 4. DC operating voltage output DC 0-300V adjustable.

 5.Single phase AC 220V output (fixed value plug type) two groups

 6.3 phase 4 line AC 380V output (fixed value wiring port) one group.

 7.Necessary output units to be increased output protection and equipped with air switch.

 8. Power supply: AC 110V/115V/120V/127V/220V/230V/240V is optional

 9.Input frequency: 50Hz/60Hz is optional


Features:


1.Reading directly: Digital meters to display current voltage power factor test value.

2. Measuring accurately: High precision test value is accurate.

3. Full protections: Each circuit is with air switch protection.

4. Portable: Small size light weight easy to move.



Q&A:


? What voltage withstand tests are required for the switchgear? ?


If the switch cabinet needs to be withstand voltage overall, it is necessary to find out what the equipment in the cabinet is, and then use the low voltage withstand standard of the components in the cabinet as the overall withstand voltage test standard;

If the main body of the switchgear is the cabinet shell and the insulator, just hit 42kV according to the standard of the insulator;

If there is a dry-type transformer inside the switchgear, the lead wire is not removed during the test, and the hardware withstand voltage is applied together. It needs to be applied to 28kV when leaving the factory and 24kV for handover;

Before the AC withstand voltage test, some things must be removed from the lead, such as the lightning arrester in the cabinet, the overvoltage absorption device, the load of the voltage transformer, the live indicator, etc.


?What is the main purpose of the high and low voltage switchgear energization test bench?


The high and low voltage switchgear energization test bench is used for the high and low voltage switchgear manufacturers to conduct various energization tests on the high and low voltage switchgear produced before leaving the factory. It can provide various AC and DC power supplies to facilitate the detection of switch cabinets and improve work efficiency.


5 out of 5 from 1 reviews

Write a review

Overal review:
Type your review:
(max 1000 characters)
Verification code:
electric in Single-phase Electric Meter Field Calibrator
https://www.mktester.com/power-analyzer/single-phase-electric-meter-field-calibrator.html ...
electric in High Pressure Wireless Phase Detector
https://www.mktester.com/electric-power-safety-tool/high-pressure-wireless-phase-detector.html

electric in High Pressure Wireless Phase Detector
https://www.mktester.com/electric-power-safety-tool/high-pressure-wireless-phase-detector.html ...
electric in Portable Single-phase Electric Meter Test Equipmen
https://www.mktester.com/power-analyzer/portable-single-phase-electric-meter-test.html